Dynamical Correlation Functions of One-Dimensional ... - progr
DESCRIPTION. The First Alert BRK SC9120B hardwired combination smoke and carbon monoxide alarm uses an electrochemical carbon monoxide sensing technology and ...
CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
SKU. 11141-000100 ; Connect with CoroMed ; CoroMed. Newsletter SignUp. About CoroMed. About Us · Privacy Policy. CUSTOMER SERVICE. Contact Us · Customer Service ...
Are you looking for replacement parts for your sausage stuffers? Find any part you need online with The Sausage Maker.
10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Your email address will not be published. Required fields are marked *Comment * Name Email Website Save my name, email, and website in this browser for the next time I comment.
WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).
Important: Read all instructions before starting the installation.WARNING: This kit must be installed by a qualified installing agency and in accordance with local codes and ordinances. Failure to properly install the conversion kit as described herein may damage the equipment and/or the home, can create a fire or asphyxiation hazard, violates U.S. listing requirements, and will void the warranty.FOR YOUR SAFETYWHAT TO DO IF YOU SMELL GASDo not try to light any appliance.Do not touch any electric switch; do not use any phone in your building.Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.If you cannot reach your gas supplier, call the fire departmentGeneralThis conversion kit can be used to change the rated firing rate (input) of your CMF/CMF2 80 convertible furnace (either PG or PO) from the factory set rate of 75,000 BTU/H. The input can be either increased to 85,000 (CMF: 90,000) BTU/H or decreased to 65,000 BTU/H with the appropriate conversion kit. This set of instructions assumes that you are familiar with and have the Installation Instructions delivered with the CMF/CMF2 furnace. Before Starting the Conversion First check your kit components to ensure that all of the necessary items are enclosed. The components of each kit are listed below: CMF/CMF2 80 PG Convertible 75 to 65 KBTU/H InputConversion KitMain Burner OrificesOne Nat. Gas OrificeOne Propane (LP) Gas OrificeConversion Kit Label (consists of four overlay labels).NOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion FURNACE NAMEFURNACE MODEL 65 PG 65 PO 90 PG 90 POCMF2710670710671710672710673CMF155941155942155943155944Table 1. Conversion Kit Label NumberCMF/CMF2 80 PG Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Main Burner OrificesOne Nat. Gas OrificeOne LP Gas OrificeConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.LP AccessoriesInstallation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
CMF/CMF2 80 PG Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Main Burner OrificesOne Nat. Gas OrificeOne LP Gas OrificeConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.LP AccessoriesInstallation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
UR18650A Datasheet, Features, Application. UR18650A Cell . Manufacture Sanyo. star-2 71. UR18650A - Cell · Manufacture Panasonic. star-1 11. UR18650A - Cell.
To Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
WARNING: This kit must be installed by a qualified installing agency and in accordance with local codes and ordinances. Failure to properly install the conversion kit as described herein may damage the equipment and/or the home, can create a fire or asphyxiation hazard, violates U.S. listing requirements, and will void the warranty.
F. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Remove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
CMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Nat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea Level
D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
The Firing Rate Conversion Kit #903099, 903100, 903101, and 903102 is designed for Model Series CMF2/CMF 80-PG Convertible and CMF2/CMF 80-PO Convertible Furnaces. This kit allows you to change the rated firing rate (input) of your furnace from the factory set rate of 75,000 BTU/H. The input can be increased to 85,000 (CMF: 90,000) BTU/H or decreased to 65,000 BTU/H with the appropriate conversion kit. Proper installation of this kit is essential for safety and to avoid damage to the equipment.
As you were browsing something about your browser made us think you were a bot. There are a few reasons this might happen:
Maxx Air logo, a brand name by Ventamatic which has been making ventilation products since ...
#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea Level
13 May 2019 — Preview of coolix. coolix by elli0777. simple...cool....basically amazing. You'll need Firefox to use this theme. Download Firefox and get the ...
Prior to starting the conversion process, ensure that you have all the necessary components included in your specific kit. Converting the Firing Rate of the CMF/CMF2 80 PG Series Furnaces
... Fitness equipment movers will handle your exercise machines with care and a ... repair and service all types of commercial and home Hoist Fitness machines.
D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Table 1. Conversion Kit Label NumberCMF/CMF2 80 PG Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Main Burner OrificesOne Nat. Gas OrificeOne LP Gas OrificeConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.LP AccessoriesInstallation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
A. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Specifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
This conversion kit can be used to change the rated firing rate (input) of your CMF/CMF2 80 convertible furnace (either PG or PO) from the factory set rate of 75,000 BTU/H. The input can be either increased to 85,000 (CMF: 90,000) BTU/H or decreased to 65,000 BTU/H with the appropriate conversion kit. This set of instructions assumes that you are familiar with and have the Installation Instructions delivered with the CMF/CMF2 furnace. Before Starting the Conversion First check your kit components to ensure that all of the necessary items are enclosed. The components of each kit are listed below: CMF/CMF2 80 PG Convertible 75 to 65 KBTU/H InputConversion KitMain Burner OrificesOne Nat. Gas OrificeOne Propane (LP) Gas OrificeConversion Kit Label (consists of four overlay labels).NOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion FURNACE NAMEFURNACE MODEL 65 PG 65 PO 90 PG 90 POCMF2710670710671710672710673CMF155941155942155943155944Table 1. Conversion Kit Label NumberCMF/CMF2 80 PG Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Main Burner OrificesOne Nat. Gas OrificeOne LP Gas OrificeConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.LP AccessoriesInstallation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea Level
This website is an independent publication and is neither affiliated with nor endorsed by any of the trademark owners. The "Bluetooth®" word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. The "Wi-Fi®" word mark and logos are registered trademarks owned by the Wi-Fi Alliance. Any use of these marks on this website does not imply any affiliation with or endorsement.
Sprayon SC0848000 EL848 Electrical Degreasers 13 oz Aerosol Can;12EA/CS. EL848 FLASH FREE® ELECTRICAL DEGREASER. Sprayon EL848 Flash Free Electrical Degreaser ...
Please refer to the detailed Installation Instructions provided with your specific kit for step-by-step guidance on converting the firing rate of your CMF/CMF2 80 PG Series Furnace. It is important to follow all instructions carefully and to have the conversion kit installed by a qualified professional in accordance with local codes and ordinances to ensure proper installation and avoid any safety hazards or damage to the equipment.For Model Series CMF2/CMF 80-PG Convertible and CMF2/CMF 80-PO Convertible FurnacesImportant: Read all instructions before starting the installation.WARNING: This kit must be installed by a qualified installing agency and in accordance with local codes and ordinances. Failure to properly install the conversion kit as described herein may damage the equipment and/or the home, can create a fire or asphyxiation hazard, violates U.S. listing requirements, and will void the warranty.FOR YOUR SAFETYWHAT TO DO IF YOU SMELL GASDo not try to light any appliance.Do not touch any electric switch; do not use any phone in your building.Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.If you cannot reach your gas supplier, call the fire departmentGeneralThis conversion kit can be used to change the rated firing rate (input) of your CMF/CMF2 80 convertible furnace (either PG or PO) from the factory set rate of 75,000 BTU/H. The input can be either increased to 85,000 (CMF: 90,000) BTU/H or decreased to 65,000 BTU/H with the appropriate conversion kit. This set of instructions assumes that you are familiar with and have the Installation Instructions delivered with the CMF/CMF2 furnace. Before Starting the Conversion First check your kit components to ensure that all of the necessary items are enclosed. The components of each kit are listed below: CMF/CMF2 80 PG Convertible 75 to 65 KBTU/H InputConversion KitMain Burner OrificesOne Nat. Gas OrificeOne Propane (LP) Gas OrificeConversion Kit Label (consists of four overlay labels).NOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion FURNACE NAMEFURNACE MODEL 65 PG 65 PO 90 PG 90 POCMF2710670710671710672710673CMF155941155942155943155944Table 1. Conversion Kit Label NumberCMF/CMF2 80 PG Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Main Burner OrificesOne Nat. Gas OrificeOne LP Gas OrificeConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.LP AccessoriesInstallation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Kit ComponentsCMF/CMF2 80 PG Convertible 75 to 65 KBTU/H Input Conversion Kit:Main Burner Orifices (One Natural Gas Orifice and One Propane (LP) Gas Orifice)Conversion Kit Label (four overlay labels)Installation Instructions for firing rate conversionCMF/CMF2 80 PG Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Main Burner Orifices (One Natural Gas Orifice and One LP GasOrifice)Conversion Kit LabelLP AccessoriesInstallation Instructions for firing rate conversionCMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelInstallation Instructions for firing rate conversionCMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelBurner HeadInstallation Instructions for firing rate conversionProduct Usage InstructionsBefore Starting the ConversionPrior to starting the conversion process, ensure that you have all the necessary components included in your specific kit. Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off the Gas to the Appliance:Set the thermostat to OFF or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move it to OFF. DO NOT FORCE THE LEVER.Please refer to the detailed Installation Instructions provided with your specific kit for step-by-step guidance on converting the firing rate of your CMF/CMF2 80 PG Series Furnace. It is important to follow all instructions carefully and to have the conversion kit installed by a qualified professional in accordance with local codes and ordinances to ensure proper installation and avoid any safety hazards or damage to the equipment.For Model Series CMF2/CMF 80-PG Convertible and CMF2/CMF 80-PO Convertible FurnacesImportant: Read all instructions before starting the installation.WARNING: This kit must be installed by a qualified installing agency and in accordance with local codes and ordinances. Failure to properly install the conversion kit as described herein may damage the equipment and/or the home, can create a fire or asphyxiation hazard, violates U.S. listing requirements, and will void the warranty.FOR YOUR SAFETYWHAT TO DO IF YOU SMELL GASDo not try to light any appliance.Do not touch any electric switch; do not use any phone in your building.Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.If you cannot reach your gas supplier, call the fire departmentGeneralThis conversion kit can be used to change the rated firing rate (input) of your CMF/CMF2 80 convertible furnace (either PG or PO) from the factory set rate of 75,000 BTU/H. The input can be either increased to 85,000 (CMF: 90,000) BTU/H or decreased to 65,000 BTU/H with the appropriate conversion kit. This set of instructions assumes that you are familiar with and have the Installation Instructions delivered with the CMF/CMF2 furnace. Before Starting the Conversion First check your kit components to ensure that all of the necessary items are enclosed. The components of each kit are listed below: CMF/CMF2 80 PG Convertible 75 to 65 KBTU/H InputConversion KitMain Burner OrificesOne Nat. Gas OrificeOne Propane (LP) Gas OrificeConversion Kit Label (consists of four overlay labels).NOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion FURNACE NAMEFURNACE MODEL 65 PG 65 PO 90 PG 90 POCMF2710670710671710672710673CMF155941155942155943155944Table 1. Conversion Kit Label NumberCMF/CMF2 80 PG Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Main Burner OrificesOne Nat. Gas OrificeOne LP Gas OrificeConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.LP AccessoriesInstallation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 65 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Installation Instructions for firing rate conversion.CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H Input Conversion Kit:Oil Burner NozzleConversion Kit LabelNOTE: Appropriate conversion kit label should be chosen based on the furnace model (see Table 1). Overlay the conversion kit label between “PERFORMANCE DATA” and “STANDARD” of the furnace name plate label.Burner HeadInstallation Instructions for firing rate conversion.Converting the Firing Rate of the CMF/CMF2 80 PG Series FurnacesTo Turn Off Gas to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.Push in the gas control lever and move to OFF. DO NOT FORCE LEVER.WARNING: Both propane (LP) and natural gas orifices are included with this kit. Make sure you install the proper orifice, and discard the old orifices (both Nat. and LP).Orifices for CMF/CMF2 80 PG Conv.Fired at 65 KBTU/HLPNat. Gas#43#24Orifices for CMF2 80 PG Conv.Fired at 85 KBTU/HLPNat. Gas#37#18Orifices for CMF 80 PG Conv.Fired at 90 KBTU/HLPNat. Gas#36#160-2000’ Above Sea LevelRemove the Burner Assembly:Follow instructions “To Turn Off Gas To Appliance.”Shut off gas supply at meter.Disconnect gas burner electric cord, gas piping to burner, and thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner assembly from unit.C. Change the Main Burner Orifice:Disconnect the two wires leading to gas control valve.Remove three (3) fasteners from U-shaped manifold plate and orifice assembly.Remove the main orifice and replace it with the alternate fuel orifice supplied in this kit.Reconnect the manifold plate using the fasteners removed earlier. (Refer to step D-2).Connect two wires to gas control valve.D. Reassemble the Burner into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-4).Reconnect the gas piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leads.E. Set the Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H firing rate conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation Instructions provided with furnace.Converting the Firing Rate of the CMF/CMF2 80 PO Convertible SeriesA. To Turn Off Oil to the Appliance:Set the thermostat to “OFF” or to its lowest setting.Turn off all electrical power to the appliance.Turn the latch and open the furnace door.B. Remove the Burner Assembly:Shut off the oil supply at the tank.Disconnect electric cord, oil piping & thermostat leads.Remove three (3) fasteners holding burner in place.Remove burner from furnace.C. When Converting the CMF/CMF2 80 PO Convertible Furnace to 85,000 BTU/H (CMF: 90,000 BTU/H)Note: the Burner Head will Need to be Replaced.For CMF/CMF2 80 PO Convertible 75 to 85/90 KBTU/H conversions, remove the burner head from the oil burner & replace it with the head in the kit. (See the Replacement Parts List for description of burner head).D. Remove the Oil Nozzle and Replace it with the Nozzle from the KitFurnaceInputNozzleHeadBTU/HCMF2CMFCMF2/CMF65,000.50 GPH, 080, AF3F0CMF285,000.65 GPH, 080, AF3–CMF90,000.65 GPH, 080, B–F3HE. Reassemble the Burner Assembly into the Furnace.Reposition the burner back into the furnace and secure with three (3) fasteners removed earlier. (Refer to step B-3).Reconnect the oil piping to the burner making sure of no leaks.Reconnect electric cord and thermostat leadsF. Set Blower Speed & Check Appliance Operation:Open the electric box underneath the vestibule divider on the left-hand side of the furnace. To do this remove the single screw in the center of the plate.The blower speed must be set to the one associated with the firing rate change. Connect the low-speed blower wire (red) for 75 to 65 KBTU/H conversions. Connect the high-speed blower wire (black) for 75 to 90 KBTU/H firing rate conversions.The kit has two labels included with it. The first label must be applied over the corresponding portion of the rating label. Align the label such that it covers and updates the appropriate information on the rating label. The other label included in the kit must be applied over the corresponding label on the burner to update that information. If the burner & rating plate labels are dirty clean them with water and a mild detergent.Adjust the air setting of the burner as described in the “Adjusting the Burner” section of the Installation Instructions.Open the manual shut-off valve & follow the “Operating Instructions” as outlined in the CMF/CMF2 Furnace Installation InstructionsSpecifications & illustrations subject to change without notice or incurring obligations (07/23). O’Fallon, MO, © Nortek Global HVAC LLC 2023. All Rights Reserved.10459670 (Replaces 707798D)Documents / ResourcesNortek 903102 CMF Firing Rate Conversion Kit [pdf] Instruction Manual903099, 903100, 903101, 903102, 903102 CMF Firing Rate Conversion Kit, CMF Firing Rate Conversion Kit, Firing Rate Conversion Kit, Rate Conversion KitReferencesUser Manual
Apr 6, 2014 · . Havaianas 4 Nite. Havaianas 4 Nite (White/White) Php 1,045.00. Rechie Jan Emolaga and 78 others. 79. 9. 4. Hzl Nutzs. I lyk... lets buy..
Vinnic Alkaline L1028 Battery(A23) ... Works in the following Remote Training Transmitters: ... Battery Specifications: Voltage: 12 Volt; Capacity: 40mAH; Length: ...
Neil
Neil